Packing-factor capacity (the one used to pick reels): usable annulus volume × packing factor ÷ rope cross-section area. This is the engineering spreadsheet's method. For standard reels, the usable diameter is the flange minus NEMA's clearance on each side (Section 7.1.3): 1 in or one rope diameter, whichever is larger, plus 3 in for the tire on RMT reels. The specific-reel check deducts no clearance, so it matches the spreadsheet.
NEMA 7.1 estimate (shown for comparison): the standard's round-cable formula, built on 5% nesting and 95% traverse use. Layers = ⌊(A − 2X − B) ÷ 1.9D⌋, turns per layer = ⌊0.95C ÷ D⌋, feet = ⌊0.2617 × (B + layers × 0.95D) × layers × turns⌋. It assumes cable wound evenly, so it's usually a poor fit for fluffy rope.
Weight check: rope weight is compared with the table's maximum capacity, which Section 1.2 defines as the total cable weight the reel can carry. Where the printed lb and kg values disagree, the lower one is used.
Written for electrical cable insulation types. The standard doesn't cover fiber rope. These multiples are not for installation.
Covering levels (Section 4.1): 1 none; 2 weather protector; 3 heavy-duty physical protector; 4 extra-heavy-duty physical protector; 5 export (wood lagging, 2 in nominal for reels 40 in and larger, 1 in below 40 in; Level 2 materials if containerized); 6 special packaging, which may be reduced to any lesser level.
"Cut to Specified Length" (NMFC 61175, Class 85) applies only when written on the order. It needs wood lagging, or 1/2 in foam under 0.090 in solid fiberboard (V3s), plus the damage-claim wording on the reel, packing list and bill of lading.